Quick Reference: Tablet Error Codes

ErrorNamePrimary CauseKey Resolution Step
101Unexpected Flow DetectedA flowmeter senses movement while not in use.Check valves, leaks, and wiring on that meter.
102Failed SRAMMaster controller's memory chip has failed.Contact your dealer for a replacement controller.
103Emergency StopSafety halt triggered by a hardware fault.Reboot machine & restart app.
104Low VoltageBattery below 12.3V or poor capacity.Charge battery; check ground wires.
105Critical Device MissingCAN bus cannot find a required component.Check power, then CAN bus resistance (~60 Ω).
201No FlowMeter detected no movement during a mix.Check pumps, airlocks, and filters.
202Inductor Not EmptyWeight is above "empty" threshold.Run Set Scale Empty Weight Wizard in Manual Mode.
203Flow Not StoppingFlow detected after stop or high vibration.Improve pump isolation or adjust reaction speed.
204Device MissingHardware not found on the CAN bus.Check power, then CAN bus resistance.
208Failed CAN MessageModule stopped sending updates (3-blink).Check for low voltage spikes or loose cables.
301Failed Device MsgMaster cannot send command to a module.Check power and CAN bus resistance, then verify tablet config in Diagnostics Mode.
302Failed CommTablet cannot "handshake" with machine.Reboot machine and restart the app.
401Connection LostTablet lost its link to the hardware.Check tablet power settings and distance.
900Unknown ErrorUnhandled software or logic exception.Screenshot the modal; email support@praxidyn.com.
901Missing Data ErrorA broken data link is missing information needed for a calculation (e.g. a unit conversion).Save the mix for recovery, then restart it.
902Bad Data From Machine ErrorA flowmeter reported a smaller total than its last reading.Recover the mix; check that flowmeter's wiring if it recurs.
Critical Maintenance Checklists: The "60 Ohm" Test
Section titled “Critical Maintenance Checklists: The "60 Ohm" Test”

For any communication error (105, 204, 208, 301), verify the CAN bus health — see CAN Bus Resistance Check for the full testing procedure.

Critical Maintenance Checklists: Power & Battery Health
Section titled “Critical Maintenance Checklists: Power & Battery Health”

See Power Check for the full procedure. Quick reference:

  • 12.3V: The threshold for low voltage warnings.

  • 13.8V - 14.2V: The required charging voltage to add capacity back to the battery.

  • Vibration: If the tablet reflection is blurry, your inductor needs isolation mounts to prevent Error 203.